Problem: Water splashes from fixture

Views:0     Author:Site Editor     Publish Time: 2019-04-11      Origin:Site Inquire

Problem: Water splashes from fixture.

Cause: Control stop is open wider than necessary.

Solution: Adjust control stop for desired delivery of water volume.

Cause: Water saver/conventional diaphragm assembly is installed on low consumption fixture or closet diaphragm assembly is installed on urinal fixture.

Solution: Determine the required flush volume (see label on valve or markings on fixture). Replace diaphragm assembly or relief valve for appropriate flush volume of fixture.